Last reviewed: November 2026

Once a standby generator is commissioned, three jobs belong to the owner: knowing how to check the oil, knowing what the lights mean, and knowing how to shut the unit down safely. At startup, our Generator School shows every customer how to run the generator and what to do if something looks wrong. This guide is the written version of those basics for homeowners in Fort Worth, Dallas, Plano, Frisco, Southlake and across DFW with a Generac, Kohler or Champion unit.

It supplements your owner’s manual and never replaces it. Models differ, so each step below names the manufacturer’s manual it comes from, and where a step varies by model it says to check your model’s manual. Keep that manual near the generator, or keep a copy indoors.

The short answer. Check the oil with the unit switched OFF and cooled, never while it runs, and bring it to the FULL mark without overfilling. Read the lights before you touch anything: green means ready, red means off or a fault. To shut down, use the controller’s OFF button and, during an outage, follow your manual’s breaker order first. Never clear a fault again and again without finding its cause.

Open lid of a Generac home standby generator in DFW showing the controller with its OFF, AUTO and MANUAL buttons
Under the lid: the controller buttons used in every procedure in this guide.

1. Which manual applies to your generator

Your generator’s model and serial number are on its data decal. Match them to the manual, because oil capacity, controller and lights differ between model families. These are the manuals this guide draws on:

BrandManual used hereController
GeneracOwner’s manual, 60 Hz air-cooled generators 10 kW to 24 kW (Rev. B, February 25, 2022)Guardian and Evolution, with LED lights and an LCD. Next Generation units use a different controller, so use their own manual.
Kohler (Rehlko)Operation manual TP-6905 (April 2026), models 24RCL/A, 30RCL/A and 38RCL/B/CRDC2 with RUN, OFF and AUTO buttons
ChampionOperator’s manual 100304 (22 kW, revised April 28, 2026)aXis controller with MAN, AUTO and OFF buttons and status icons

Kohler’s home generators are now part of Rehlko, so you may see either name on the maker’s site. Larger or newer models in each family can differ from the manuals above, so check your model’s manual for anything this guide does not say. Our brand guides cover Generac, Kohler and Champion equally, and Generac vs Kohler vs Champion compares them.

2. Safety basics before any step

  • Carbon monoxide. Exhaust contains carbon monoxide, a colorless, odorless gas. All three manuals say to run the unit outdoors only and keep exhaust away from windows and vents. Kohler and Champion also say to fit carbon monoxide detectors on each level of the home. If anyone feels dizzy or weak, get to fresh air at once. The CPSC safety alert gives the same advice.
  • Never service a running unit. Do not check the oil, open panels or reach near moving parts while it runs. Kohler’s manual says not to check the oil while the unit operates, and Generac warns of automatic start-up: disconnect utility power and render the unit inoperable before working on it.
  • Never add fuel while it runs. Kohler’s manual says never to add fuel to the tank while the engine is running, because spilled fuel can ignite on hot parts. Wipe up oil spills right away (Champion), and let a fuel spill dry before starting the unit (Generac).
  • Keep it clear. No rags, tools, debris or combustibles on or near the unit, and no blocked air intake or vents.
  • Follow the manual. If a step is unclear or your manual says something different, stop, follow the manual or call your dealer.

3. Checking and topping off the oil

Oil is the one fluid an owner can check. All three manuals tie the check to running time: look at it daily when the generator runs through a long outage, and keep to the maintenance schedule the rest of the year. Generac also notes the generator shuts down if the oil level is low, so the check is worth the few minutes.

Generac air-cooled, 10 kW to 24 kW

  1. Set the utility main breaker to OFF.
  2. Set the generator’s main line breaker (its disconnect) to OFF.
  3. If it was running in an outage, let it run about one minute to cool down.
  4. Press OFF on the controller, then wait five minutes.
  5. Pull the dipstick, wipe it dry, push it fully in, then pull it again.
  6. The level should be at the FULL mark. If it is low, add the recommended oil through the fill cap until it reaches FULL, then refit the dipstick and cap.

To restart, the manual has you press AUTO, let the unit warm up for a few minutes, then turn the generator breaker ON and finally the utility breaker ON.

Kohler, RDC2 units

  1. Press OFF on the controller.
  2. Remove the dipstick and wipe the end clean.
  3. Reinsert it and wait at least 30 seconds, then remove it and read the level.
  4. Keep the level between the Add and Full marks. The manual says not to run the unit below Add or above Full.

Kohler says to check every 24 hours of operation, or before the engine starts each day. Adding a little oil between changes is normal: use a funnel, add a small amount, then recheck.

Champion, aXis units

  1. If the unit is running in an outage, turn off household loads.
  2. Put the aXis controller in OFF.
  3. Pull the dipstick, wipe it dry, reinsert it fully, then pull it again.
  4. The level should be at the FULL mark. Add oil if needed, and do not overfill.

Champion says to check daily when running for an extended period, and its maintenance chart lists a monthly oil level check. Check your model’s manual for the full sequence, which also covers disabling automatic starting.

Oil type and amount vary by model, so check your model’s manual for both and use only what it lists. Overfilling can damage the engine on all three brands.

Chart separating what a homeowner can safely check on a standby generator from what a technician should handle
What an owner can check, and what is a technician’s job.

4. Reading the lights and controller

The lights show the unit’s state at a glance. Read them first, note them, and only then decide whether to act.

BrandNormal and readyNeeds attention
Generac GuardianGreen LED on when utility power is present and the controller is in AUTO. It flashes when the transfer switch moves to generator power in an outage.Red LED on when the unit is OFF or a fault is detected, so contact your dealer. Yellow LED on when maintenance is required.
Kohler RDC2AUTO LED lit in standby mode. RUN lights after a manual start.In AUTO, the OFF LED flashing quickly means a fault shutdown. Find and fix the cause before resetting.
Champion aXisIn AUTO with the unit idle, the UTILITY, ATS active and LOAD icons are lit, so the home is on utility power. Blue icons show the exercise period.A RED icon, plus the exterior warning LED on the back, means a fault. The unit shuts down and will not restart until you reset it.
  • Generac. Next Generation units use a different controller and light pattern. Generac’s status light article lists each pattern, and our Generac error codes guide covers the codes.
  • Kohler. On a warning the controller shows a message and the unit keeps running; it resets itself once the condition is corrected. A shutdown needs a reset.
  • Champion. The manual says to check the exterior warning LED weekly. Only the low battery and maintenance icons leave the unit running.
Comparison of Generac Guardian and Next Generation status light patterns for green, yellow and red
Generac status lights, Guardian compared with Next Generation.

5. Shutting the unit down safely

Three situations call for three different procedures. The controller’s OFF button is the normal stop. A shutdown during an outage, with the house running on the generator, follows a breaker order. A full shutdown for work on the unit disables automatic starting, and that is a technician’s job.

Generac air-cooled: shutting down during an outage

Generac’s manual says to follow these steps in order, to avoid equipment damage:

  1. Set the utility main breaker to OFF.
  2. Set the generator main line breaker to OFF.
  3. Let the generator run about one minute to cool down.
  4. Set the generator to OFF at the controller.
  5. Remove the 7.5 amp fuse from the controller.

The manual gives a matching restart order. Do not use the auxiliary shutdown switch to power the unit down in normal use: Generac says that damages equipment, and the switch is the emergency means of shutdown.

Kohler: stopping the unit

  • Press OFF to stop the engine. For a local start, the manual says to run the unit with no load for at least 2 minutes first so it cools down.
  • With an automatic transfer switch, the unit runs without load after utility power returns, then stops on its own.
  • To disable it before service, Kohler lists: press OFF, disconnect power to the battery charger if fitted, then remove the battery cables, negative first.

Champion: stopping the unit

  • Press OFF on the aXis controller. It stops the engine and prevents automatic operation, and Champion says OFF is required whenever maintenance or service is performed.
  • The unit also has generator ON/OFF switches. Turned off, they shut it down and keep it from starting for any reason. Champion says to use them when the unit must stay off whatever the utility does.
  • To prevent an accidental start while panels are open, the manual has you pull the controller fuse and disconnect the battery cables, negative first.

Do not leave a unit switched off. A generator left in OFF, or with its breaker open, will not power the house in the next outage. Return it to AUTO and the breaker positions your manual describes.

6. Faults: reset only after finding the cause

  • Generac. Note the code or message. The manual’s reset is to press OFF, then ENTER. If the alarm comes back, contact your dealer.
  • Kohler. Find and correct the cause first. Then press OFF to reset, or use the controller menu, and press AUTO.
  • Champion. Push OFF to reset, then AUTO to re-arm.

On all three, a fault that returns is a reason to call, not to keep resetting. Leave the message showing for the technician when you can. Our guides to what to check when a standby generator won’t start and Generac error codes cover the next steps.

7. What to leave to a technician

  • Fuel line and gas pressure work, and anything with a gas smell: move away and call your gas utility.
  • Wiring in the generator, transfer switch or panel.
  • Battery replacement and work behind panels. Generac recommends that maintenance be done by an Independent Authorized Service Dealer.
  • Warranty work, which goes through the manufacturer’s dealer network.

To be fair, the oil check and a look at the lights are a few minutes of work that need no visit from us. The maintenance visit covers the rest: oil and filter changes, the battery and the system test. How a standby generator works explains the parts, and using a generator during an outage covers the first night.

8. Help from HomeSafe

HomeSafe is a Generac PowerPro Premier dealer, and a dealer and installer for Kohler and Champion. If a light or message is unclear, call (817) 439-9009. Emergency service is available 24/7, every day including holidays. After-hours and emergency rates apply depending on the circumstances, and you are told what they are before a technician is dispatched. Generator service and repair explains how it works, service during a storm covers outages, and the DFW service area page lists the cities we serve.

In this series: what maintenance includes · Generac error codes · when a generator won’t start · standby generator battery and charger checks · remote monitoring options · signs your generator needs service · repair or replace

Quick answers

How often should I check my generator’s oil?

Every 24 hours of running during a long outage. Kohler says every 24 hours of operation or before the engine starts each day, and Generac and Champion say daily during extended runs. Otherwise follow your model’s maintenance schedule.

Can I check the oil while the generator is running?

No. Press OFF and let it cool first. Kohler says not to check the oil while the unit operates, and Generac has you wait five minutes after pressing OFF before reading the dipstick.

What do the green, yellow and red lights mean?

On a Generac Guardian, green is ready, yellow is maintenance due and red is OFF or a fault. Kohler and Champion show their state differently: Kohler lights OFF, AUTO or RUN, and Champion shows icons. Check your model’s manual for the exact pattern.

How do I shut down my standby generator manually?

Use the OFF button on the controller, and during an outage follow your manual’s breaker order first. On Generac air-cooled units that means the utility main, then the generator breaker, a one-minute cool-down, then OFF. Check your model’s manual for the exact order.

Can I just clear a fault and restart the generator?

Not before you know the cause. All three manuals say to correct the cause before resetting, or to contact a dealer when a fault returns. If the same fault comes back, call rather than clearing it again.

When should I call a technician instead?

Call for a gas smell, wiring, fuel line, battery or panel work, or a fault that keeps returning. Checking the oil and reading the lights are the owner’s jobs; anything inside the unit is not.